Product Name: 2-fold Relay Amplifier 32 100
Supply Ability:
Related proudcts hiam module,
Specifications Planar F/4
Price Term:
Port of loading:
Minimum Order
Unit Price:

2-fold Relay Amplifier 32 100
safety-related
Switching voltage 24 V DC / 24 V AC
The module is TV tested according to DIN V 19250 for RC 1...7,
according to IEC 61508 for SIL 4 and EN 954-1 to Cat 4.
The module is equipped with diverse relays according to the standards
DIN V VDE 0801 A1 and DIN VDE 0116.
Thus the amplifier can be used for safety shutdowns, e. g. to cut off the
entire fuel supply for incinerator plants (DIN VDE 0116/10.89, item 8.7.2).
Output 1 floating NO contact each (sealed)
Contact data: cf. reverse
Switching time (contact) approx. 10 ms
Reset time (contact) approx. 12 ms
Switching time (signal) approx. 3 ms
Reset time (signal) approx. 8 ms
Operating data 24 V DC / 135 mA
***ce requirement 3 U high, 4 SU
32 100
RDY
ERR
OC1
FF1
OC2
FF2
F2
F1
F1, F2 Delivery state 4 A time-lag
32 100 (0128)
2/4
The relay amplifier has a safe isolation of the inputs resp. the power supply
from the output contacts, according to EN 50178 (VDE 0160). The
clearence in air and the creepage distance are dimensioned for overvoltage
class III up to 300 V.
The output contacts are isolated one from each other up to 250 V according
to VDE 0110-1, overvoltage class III.
Closing of the relay contacts d2-d4 (d8-d10) is indicated by OC1 (OC2). A
tripped fuse F1 (F2) is signalized by the output z14 (d14) and with the LED
FF1 (FF2). The outputs z14 and d14 are not safety-related; they are suitable
for connection to a busbar.
Relay contact
Contact material AgNi, gold-plated
Switching voltage 24 V DC / 24 V AC
Switching current £ 4 A, ³ 10 mA
Inrush peak current £ 12 A for 1 s (non-periodic)
Fusing 4 A time-lag (delivery state)
Switching AC £ 120 VA, cos j > 0.5
capacity DC £ 120 W, non-inductive load
Bounce time approx. 1.5 ms
Switching frequency £ 10 cycles/second
Life
mechanical > 107 cycles
electrical > 2.5 x 105 cycles at resistive load
and £ 0.1 cycles/second
All functions on the module including the output contacts with the fuses are
monitored by a micro-controller

Contact Us
Company: Asia Science&Technology Co***ny Limited
Contact: Mr. Ethan Wen
Address: Unit 04, 7/ F, Bright Way Tower,No. 33 Mong Kok Road, Kowloon, HK.
Postcode:
Tel: 00852-27935511
Fax: 00852-35902333
E-mail:         


Copyright© Asia Science&Technology Co***ny Limited All Rights Reserved.
Tel : 00852-27935511 Fax : 00852-35902333
Powered by 86exporter.com